China Outdoor Vacuum Circuit Breaker for Power Distribution System Manufacturer, Supplier, Factory

Outdoor Vacuum Circuit Breaker for Power Distribution System | Kexun Electric

Kexun Electric Co., Ltd. is a China supplier of 40.5 kV switching gear built for outdoor networks, and this ZW7-40.5 frame is offered as an Outdoor Vacuum Circuit Breaker for Power Distribution System duties on feeders and overhead sections that need a reliable interrupting point. The unit carries 1250 to 2500 A continuously, breaks 25 or 31.5 kA and holds a 185 kV lightning impulse level, which places it at the voltage boundary between bulk transmission and the branches that actually reach the load. At 600 kg in a stainless steel box, it is sized for the places a substation building is not justified but a firm switching point is still required.

Where Feeders Need Switching

A distribution feeder needs a point that can be opened for maintenance, sectionalised after a fault and reclosed when the line is clear. The breaker sits at that point, isolating a section so that the rest of the feeder stays live while work proceeds on the isolated stretch.

The Switching Job Itself

1. Load switching: open and close the feeder under normal load at 1250 to 2500 A.

2. Fault clearing: interrupt 25 or 31.5 kA short-circuit current when protection trips.

3. Auto-reclose: follow the rated sequence to reclose after a transient fault.

An Outdoor Vacuum Circuit Breaker for Power Distribution System use is chosen here first for its interrupting rating, then for the mechanical life that lets it repeat the cycle season after season.

Overhead Line Sections

On an overhead distribution network, sections are divided so that a downed conductor or a tree contact takes out only one section rather than the whole outgoing feeder. The breaker marks one such division, mounted on a pole structure or a small gantry at the line side.

Why the Frame Is Built This Way

Three poles in one stainless steel box keep the erection to a single lift at 600 kg, and the 700 ± 2 mm phase spacing matches common pole-top steel. Ambient range is −30 to 60 °C, altitude below 3000 m and wind speed up to 34 m/s, so the same unit serves a northern winter line and a tropical coastal one.

For an overhead section, an Outdoor Vacuum Circuit Breaker for Power Distribution System duty is expected to sit outside, sealed against pollution grade IV, and still operate after a storm without an on-site crew.

Incoming Bays and Substations

Small outdoor substations and incoming bays take the same breaker as the feeder end, because the duty is comparable: interrupt fault current, carry load current, and hold the insulation level against lightning. The 40.5 kV class, 185 kV impulse and 95 kV across the open break are what let it stand at the boundary of a compact substation.

Number

Item

Unit

Data

1

Contact distance

mm

20±2

2

Contact overtravel

mm

4±0.5

3

Opening speed

m/s

1.4-1.8

4

Closing speed

m/s

0.4-0.8

5

Contact closing bounce time

ms

≤5

6

Phase to phase distance

mm

700±2

7

Different periods of three-phase opening and closing

ms

≤2

8

Resistance of each phase conductive loop

μΩ

<80

9

Closing time

ms

≤100

10

Opening time

ms

≤50

11

Weight

Kg

600

Single Bay, One Frame

Because the mechanism, the poles and the optional current transformer share one box, an incoming bay needs a single foundation and a single set of secondary cables rather than a row of individual poles. That shortens the civil work and the wiring time on a small site.

This is the same Outdoor Vacuum Circuit Breaker for Power Distribution System selection logic whether the bay feeds a rural village or a small industrial load: match the fault level, allow headroom, and rely on the 10,000-operation mechanical life.

Rating Headroom for Load Growth

Distribution load grows slowly but steadily. A feeder sized today for 1250 A may carry closer to 2500 A in a decade, and the fault level at the substation can rise as more generation and more cable are added. Choosing the interrupting class one step above the calculated value is the usual hedge.

Number

Item

Unit

Data

1

Rated voltage

kV

40.5

2

Rated current

A

1250~2500

3

Rated frequency

Hz

50或60

4

Working frequency withstand voltage1min(wet)(dry)

P to P、to earth/break

kV

80 /90/95

5

Lightning impulse withstand voltage(peak)     P to P、to earth/break

kV

185

6

Rated short circuit break current

kA

25/31.5

7

Rated short circuit close current(peak)

kA

63/80

8

Rated peak withstand current

kA

63/80

9

4S short-term withstand current

kA

25/31.5

10

Rated operation circle

 

分-0.1s-CO-3s-CO-6sCO-60s

11

Rated short circuit current breaking times

time

30

12

Mechanical life

time

10000

13

Control voltage

V

AC/DC220

14

Secondary circuit 1min working frequency voltage

KV

2

1. Rated current: 1250 to 2500 A, so the frame covers light and dense branches.

2. Breaking class: 25 kA or 31.5 kA, with making and peak withstand at 63 or 80 kA.

3. Short-time: a 4 s withstand equal to the breaking current lets protection discrimination work.

An Outdoor Vacuum Circuit Breaker for Power Distribution System duty is normally taken with the higher breaking class when the future fault level is uncertain, because upgrading the frame later is far costlier than specifying it now.

Coordination With Protection

The breaker does not decide what to interrupt; the protection relay does. The unit supplies the current input through the optional current transformer, the trip command through the over-current trip coil, and the position feedback through auxiliary contacts, so the relay scheme can be built around it.

What the Owner Should Specify

1. Transformer option: order the integrated current transformer when metering or protection is picked up at the breaker.

2. Control supply: AC/DC 220 V covers the usual station battery and auxiliary arrangements.

3. Trip coil: the over-current trip coil operates on fault current independently of the control supply.

Kexun Electric Co., Ltd. develops and builds transmission and distribution equipment at 35 kV and below, with output split about 80% to the domestic market, 16% to Southeast Asia and 4% to Oceania. The export sales managers handle enquiries in English, which matters when a feeder specification crosses a border.

Coordination details are what turn an Outdoor Vacuum Circuit Breaker for Power Distribution System duty into a working protection scheme, and they are the details discussed before the order rather than after energisation.

Frequently Asked Questions

Q: What voltage class is the unit built for?

A: The frame is rated 40.5 kV for 35 kV networks, with power-frequency withstand of 80 kV wet and 90 kV dry, and a 185 kV lightning impulse level across the relevant clearance paths.

Q: Which breaking class should a distribution feeder take?

A: Compare the calculated fault level against 25 kA and 31.5 kA, then choose one step above when growth is expected. The making and peak withstand figures follow at 63 kA and 80 kA, and the 4 s short-time withstand matches the breaking current.

Q: Does the breaker include current transformers?

A: The transformer set is an option chosen by the user. Order it fitted when metering or protection is taken from the breaker, or order the frame without it when protection lives in a separate panel.

Q: What outdoor conditions does the unit accept?

A: Ambient temperature runs −30 to 60 °C, altitude stays below 3000 m, wind speed is limited to 34 m/s and pollution grade is IV. Storage range is −40 to 85 °C, so winter stocking in an unheated yard is within the declared range.

Q: How is the unit mounted on an overhead line?

A: The whole three-phase body weighs 600 kg and mounts on a compact steel structure, with 700 ± 2 mm phase-to-phase spacing. A small crane or pole-mounted winch handles the lift, and the stainless box needs no extra weather hood.

Q: Where does the manufacturer sell?

A: Output is about 80% domestic, 16% Southeast Asia and 4% Oceania, and the company builds equipment at 35 kV and below. Export enquiries are handled by sales managers who work in English without a relay.

Q: What is the minimum order and payment?

A: The minimum order is one set, standard models are held in stock and payment is by T/T or L/C. Custom work to drawings or samples is accepted after a pre-production discussion and buyer confirmation.

Q: Can I see test records before shipment?

A: The QC department works to TQM, and photos or video of production and testing can be shared before dispatch. The company holds ISO9001, ISO14001, ISO45001, Type Test and CCC certification.

Hot Products

  • Pre-installed American Box Type Cabinet

    Pre-installed American Box Type Cabinet

    Kexun is a power transmission and transformation equipment factory in China. Its beauty Pre-installed American Box Type Cabinet is well known for its good protective performance, high standardization, simple maintenance and wide applicability.
    Model: ZBW-12
    Brand:KEXR
  • GN38 Type Indoor HV Disconnector

    GN38 Type Indoor HV Disconnector

    The GN38 type indoor HV disconnector produced by China supplier is equipped with coaxial locking and perfect mechanical interlocking mechanism, which is compact and compact in appearance. It is designed and manufactured to meet the needs of the compact development of fixed high-voltage cabinets and ring network cabinets, and is the best switch for compact box-type switchgear.
    Model: GN38
    Brand:KEXR
  • Gas Insulated Electrical Panel

    Gas Insulated Electrical Panel

    KXRM6-12 Gas insulated electrical panel independently developed and produced by Kexun Electric is widely used in 10kV/6K distribution system. Switch cabinet is modular unit mode, which can be combined according to different purposes; There are two categories: fixed unit combination and expandable unit, which meet the needs of flexible use of compact switchgear in various substations and are the first choice switch products for various urban and rural users' power distribution systems.
    Model: KXRM6-12
    Brand:KEXR
  • AC Low Voltage Distribution Cabinet

    AC Low Voltage Distribution Cabinet

    GGD Type AC low voltage distribution cabinet produced by China manufacturer Kexun is suitable for AC 50Hz distribution system of power users such as power plants, substations, factories and mines, with rated working voltage of 380V and rated working current of 3150. It is used for power conversion, distribution and control of power, lighting and distribution equipment.
    Model:GGD
    Brand:KEXR
  • Environmental Protection Unit

    Environmental Protection Unit

    KXHXGN-12 type Environmental Protection unit produced by KEXR, a power transmission and distribution equipment supplier in China, is a 12kV gas-insulated ring network cabinet with environmental protection gas (such as dry air, nitrogen or mixed gas) as insulation medium, which is suitable for ring network power supply, terminal power supply and small-scale opening and closing stations of distribution networks.
    Model: KXHXGN-12
    Brand:KEXR
  • Box Type Fixed Metal Closed Switch Equipment

    Box Type Fixed Metal Closed Switch Equipment

    The main primary components of XGN2-12 Box Type Fixed Metal Closed Switch Equipment specially produced by Kexun in China Factory are all redesigned. Compared with the handcart equipment and GG-1(A)F equipment which are mainly used at present, XGN2-12 Box Type Fixed Metal Closed Switch Equipment has higher insulation level and protection level, and no phase-to-phase and phase-to-ground clapboards and insulating gas are used inside, and no secondary plug is used in the secondary circuit.
    Model:XGN2-12
    Brand:KEXR

Send Inquiry